DS 500 -intelligent chart recorder for compressed air and gases

Article no: 0500 5000

From recording of the measured data, automatic sensor identification, indication on a big colour screen, alerting, storage up to remote read-out via webserver … this is all possible with DS 500. By means of the CS Soft software alarms can be sent via SMS or e-mail. On the big 7" colour screen with touch panel all information are available at a glance. The operation is very easy.

All measured values, measured curves and threshold exceedings are indicated. The curve progressions from the beginning of the measurement can be viewed by an easy slide of the finger. Daily/weekly/monthly reports with costs in € and counter reading in m³ for each consumption sensor are completing the sophisticated system concept. The big difference to ordinary paperless chart recorders reveals in the easy initiation and in the evaluation of the measured data. All sensors are identified directly and powered by DS 500. Everything is matched
and tuned.

No time consuming studying of the instruction manual … this saves time. Internal voltage supply of all sensors, no wiring of external mains units … this saves additional costs.

Advantages at a glance:
- Clear layout: 7" colour screen with touch panel
- Versatile: Up to 12 optional sensors can be connected…
- Easy: Very easy operation, automatic sensor identification…
- Reliable: Stores all measured values reliably, 4 alarm relays for threshold exceedings...
- Suitable for industrial applications: Metal housing IP 65 or panel mounting…
- Data available though world wide web: Network-compatible and remote transmission via webserver
- Intelligent: Daily/weekly monthly reports…
- … Saves time and costs during installation

Add to your enquiry list

Dimensions of housing280 x 170 x 90 mm, IP 65
Connections18 x PG 12 for sensors and supply, alarm relays
1 x RJ 45 Ethernet connection
Version panel mountingCutout panel 250 x 156 mm
Weight:
7.3 kg
MaterialDie cast metal, front screen polyester
Sensor inputs4/8/12 sensor inputs for analogue and digital sensors
freely allocatable. See options
Digital CS sensors for dew point and consumption with SDI
interface FA/VA 400 Series,
Digital third-party sensors RS 485 / Modbus RTU, other
Bus systems realizable on request
Analogue CS sensors for pressure, temperature, clamp-on
ammeters preconfigured
Analogue third-party sensors 0/4 ..20 mA, 0..1/10/30V, pulse,
Pt 100 / Pt 1000, KTY
Power supply for
sensors

Output voltage: 24 VDC ± 10% galvanically isolated
Output current: 130 mA  non-stop operation*, Peak 180mA
*maximum output current over all channels with
- one power supply: 400m
- second power supply (optional): 1A

InterfacesUSB stick, USB cable, Ethernet / RS 485 Modbus RTU / TCP,
SDI other bus systems on request, WEB server optionally
Outputs4 relay (max. switching voltage: 400 VAC / 300 VDC, min circuit current of 10mA 6A..), Alarm management,
Programmable relay, general alarm
Analog output, impulse for sensors with own
Output signal looped through e.g. VA / FA Series
Memory cardMemory size 2 GB SD memory card standard,
optionally up to 4 GB
Power supply100...240 VAC / 50-60 Hz, special version 24 VDC
Colour screen7" touch panel TFT transmissive, graphics, curves, statistics
Accuracysee sensor specifications
Operating temperature0...50°C
Storage temperature-20...70°C
OptionallyWeb server
OptionallyQuick measurement with 10 ms sampling rate for analogue sensors,
Max/Min indication per second
OptionallyOption "consumption report” statistics,
daily/weekly/monthly report

 

Input signals

Current signal
internal or external power supply
Measuring range
Resolution
Accuracy
Input resistance


(0...20mA/4...20mA)
0…20 mA
0,0001 mA
± 0,003 mA ± 0,05 %
50 Ω

Voltage signal
Measuring range
Resolution
Accuracy
Input resistance

(0...1 V)
0…1 V
0,05 mV
± 0,2 mV ± 0,05 %
100 kΩ

Voltage signal
Measuring range
Resolution
Accuracy
Input resistance
(0...10 V / 30 V)
0…10 V
0,5 mV
± 2 mV ± 0,05 %
1 MΩ
RTD Pt 100
Measuring range
Resolution
Accuracy

-200…850° C
0,1° C
± 0,2°C (-100...400°C)
± 0.3°C (further range
RTD Pt 1000
Measuring range
Resolution
Accuracy

-200…850° C
0,1° C
± 0,2° (-100...400°C)
Pulse
Measuring range

min pulse length 400 μs
frequency 0...1 kHz
max. 30 VDC
bar high: 2.5V
bar low: 0.7V

Feedback


(*) required