Flow station DS 300 for existing pipelines

Article no: 0600 4005

DS 300 displays the actual value (m³/h, m³/min) and the total consumption. A 4...20 mA output for m³/h and a pulse output for m³ are available for routing to a superior building management system (PLC).

The large measuring range of the consumption sensors enable the recordings of high consumptions (e.g. on weekdays) and the determination of leakage of a few litres/min (e.g. weekends).

Flow station DS 300 with consumption counter consisting of:

Multifunction measuring instrument DS 3000500 3000
Consumption probe VA 400 in basic version0695 4001
Connection cable, length: 5 m0553 0104
Plug-in wiring and configuration of flow station0990 0010

Special features

  • Usable from 1/2" to 12" (DN 300)
  • All-in-one solution, small installation expenditure
  • 2 displays, actual flow and total consumption
  • Easy installation and removal of the sensor under pressure
  • Highest accuracy due to 5 point precision calibration
  • Output 4 to 20 mA for m³h, pulse output for m³
  • Easy handling:
    - Inner diameter freely adjustable in DS 300
    - 2 alarm values freely adjustable
    - Optical display in case of alarm
    - Consumption counter resetable
  • Dew point sensor connectable

Add to your enquiry list

 DS 300

Dimensions:

118 x 115 x 93 mm, IP 65 (wall housing)
92 x 92 x 70 mm, IP (panel mounting)

Inputs: 

2 digital inputs for VA 400 resp. FA 410

Interface:

USB

Keypad:

4 keys

Power supply:

100-240 VAC, 50-60 Hz

Accurancy:

see VA 400

Alarm outputs:

2 relays, 230 VAC, 3 A

Operation temp.:

0...50 °C

Transport temperature:

-20...70 °C

 

 

 VA 400

Parameters:

m³/h, l/min (1000 mbar, 20°C) in case of compressed air resp. Nm³/h, Nl/min (1013 mbar, 0°C) in case of gases

Adjustable via
software:
 

m³/h, m³/min, l/min, l/s, ft/min, cfm, m/s, kg/h, kg/min

Adjustable via
keypad:

diameter for volume flow calculation, counter resettable

Meas. principle

calorimetric measurement

Sensor:

2 x silicium chip

Meas. medium:

air, gases

Gas types adjustable
via software:

air, nitrogen, argon, helium, CO2, oxygen

Accuracy:

± 4 % m.v.
± 3 % m.v. via 5 point ISO precision calibration

Operating temp.:

-30...110°C probe tube
-30...80°C housing

Operating pressure: 

up to 50 bar

Analogue output:

4...20 mA for m³/h resp. l/min; on request: scaling for cfm, m3³min, l/min, l/s, ft/min, m/s

Pulse output:

1 pulse per m³, signal high 24 VDC, for 30 ms

PC connection:

SDI interface

Power supply: 

24 VDC

Burden:

< 500 Ohm

Housing:

polycarbonate

Probe tube:

stainless steel 1.4301 mounting length 220 mm, Ø 10 mm

Mounting thread:

G 1/2"

Diameter housing:

65 mm

Feedback


(*) required