전 세계적으로 고유한 파워 빔 포밍으로 여러 누출을 동시에 감지합니다. 4세대 기술 - 다른 가스에도 적합 비용 추정 및 ISO 50001 문서화를 포함하여 누출 위치를 파악하고 수정하는 데 도움을 줍니다.
산업용 변압기는 널리 사용되며 매우 클 수 있습니다. 변압기를 제작하거나 수리할 때는 변압기가 완전히 누출되지 않았는지 확인하는 것이 중요합니다. 변압기에는 장치를 냉각하고 전기 절연을 제공하며 산화를 방지하는 데 사용되는 광유가 채워져 있기 때문에 이는 매우 중요합니다.
충전 중에 누출이 감지되면 문제를 해결하기 전에 모든 오일을 배출해야 합니다. 이는 상당한 시간과 비용 손실로 이어집니다.
At present, transformers are tested by filling them with dry air to an overpressure of 200–300 mbar. This pressure is maintained for several hours to check for any pressure drop, which indicates leaks. A higher test pressure is not possible due to the transformer’s construction. Components such as pressure relief valves, cooling fins and certain joints cannot withstand higher pressures. If a pressure drop is detected, a soapy water solution is used to locate leaks. All joints and connections are checked manually. The formation of air bubbles indicates a leak.
This method is:
It is therefore the case that leaks only become apparent once the transformer has been filled with oil and is operational.

CS INSTRUMENTS has over 20 years’ experience in ultrasonic leak detection. This technology makes it possible to detect leaks without the system needing to be on overpressure.
A compact ultrasonic tone generator is placed inside the transformer, requiring only an opening of 8 cm in diameter. Bespoke solutions are available for smaller openings. The sound source emits a powerful ultrasonic signal in multiple directions, which propagates throughout the entire transformer. An ultrasonic leak detector can then be used on the outside of the transformer to easily determine where leaks are located. Where a leak is present, the ultrasonic signal escapes and is detected by the leak detector responding to the ultrasonic tone.
Advantages of this method:
Thanks to this approach, a complete transformer can be checked for leak-tightness quickly and reliably, with a significant reduction in working hours and the risk of missed leaks.